3.10.2.
Waveform Storage
Description
Gn P/F Trig Storage
Select which elements trigger a waveform record
Gn E/F Trig Storage
As Above
Gn SEF/REF Trig Storage
As Above
Gn Misc Current Storage
As Above
Gn AFD Trig Storage
As Above
Pre-trigger Storage
Select Percentage of waveform record stored before
the fault is triggered
Record Duration
Select waveform record duration
Trigger Waveform
Trigger waveform storage
Clear Waveforms
Clear all stored waveform records
3.10.3.
Fault Storage
Description
Gn Max Fault Rec Time
Maximum time Fault record information will be stored and
classed as same fault
Clear Faults
Clear all stored fault records
3.10.4.
Event Storage
Description
Clear Events
Clear all stored event records
Data Log
Selects whether the Data Logger is enabled
Unrestricted ©2018 Siemens Protection Devices Limited
Range
Combination of ( 51-1, 51-2, 50-1, 50-2 )
Combination of ( 51N-1, 51N-2, 50N-1,
50N-2, 51G-1, 51G-2, 50G-1, 50G-2 )
Combination of ( 51SEF-1, 51SEF-2,
50SEF-1, 50SEF-2, 64H )
Combination of ( 46IT, 46DT, 37-1, 37-2,
49 Trip, 49 Alarm, 37G-1, 37G-2 )
Combination of ( AFD-1, AFD-2, AFD-3,
AFD-4, AFD-5, AFD-6)
10, 20, 30, 40, 50, 60, 70, 80, 90
10 Rec x 1 Sec, 5 Rec x 2 Sec, 2 Rec x 5
Sec, 1 Rec x 10 Sec
Range
0, 1 ... 59900, 60000
Range
7SR210 Settings Guide
Default
51-1, 51-2, 50-1,
50-2
51N-1, 51N-2,
50N-1, 50N-2,
51G-1, 51G-2,
50G-1, 50G-2
51SEF-1,
51SEF-2,
50SEF-1,
50SEF-2, 64H
--------
------
20 %
10 Rec x 1 Sec
Default
2000 ms
Default
Page 59 of 61