Sensitive Power; Reference; Operate And Reset Level; Operate And Reset Time - Siemens Argus 7SR21 Technical Manual

Overcurrent relay
Hide thumbs Also See for Argus 7SR21:
Table of Contents

Advertisement

7SR21 & 7SR22 Performance Specification
2.4
32S Sensitive Power
2.4.1

Reference

Parameter
S
32S-n Setting
s
t
32S-n Delay setting
d
2.4.2

Operate and Reset Level

Attribute
S
Operate level
op
Reset level
Variation
2.4.3

Operate and Reset Time

Attribute
Element basic
t
basicE
operate time
t
Operate time following delay
op
Disengaging time
2.4.4

Operate Threshold

Attribute
Minimum levels for
operation
Unrestricted Page 24 of 68
Over-power
Under-power
-10 °C to +55 °C
+ 2 Hz £ 5 %
f
– 3 Hz to f
nom
nom
Over-power
Under-power
I
V
Value
0.005...2 x Sn
0.00 ... 14400 s
Value
100 % Ss, ± 5% or ± 2% Sn
³ 95 % S
op
£ 105 % S
op
£ 5 %
Value
1.1 x Ss: 60 ms ± 10 ms
2.0 x Ss: 45 ms ± 10ms
0.5 x Ss: 30 ms ± 10ms
, ± 1 % or ± 10ms
t
+ t
basic
d
< 40 ms
Value
2.5 % In
2.5% Vn
© 2013 Siemens Protection Devices Limited