5.4
CT Supervision (60CTS & 60CTS-I)
The relay has two methods of detecting a CT failure, depending on the relay variant.
5.4.1
(60CTS-I) – 7SR21 & 7SR22
The current from each of the Phase Current Transformers is monitored. If one or two of the three input currents
falls below the CT supervision current setting CTS-I for more than 60CTS-I Delay then a CT failure output
(60CTS-I Operated) is given. If all three input currents fall below the setting, CT failure is not raised.
Operation of the CT supervision elements can be inhibited from: -
Inhibit 60CTS-I
60CTS-I Element
Enabled
Disabled
Inhibit 60CTS
Inhibit 60CTS
60CTS I
<
IL1
IL2
Any 2 phases
but not all 3
IL3
Figure 5.4.1-1
5.4.2
(60CTS) – 7SR22
Normally the presence of negative phase sequence (NPS) current in a power system is accompanied by NPS
voltage. The presence of NPS current without NPS voltage is used to indicate a current transformer failure.
The element has a setting for NPS current level 60CTS Inps and a setting for NPS voltage level 60CTS Vnps. If
the negative sequence current exceeds its setting while the negative sequence voltage is below its setting for
more than 60CTS Delay then a CT failure output (60CTS Operated) is given.
Operation of the CT supervision elements can be inhibited from: -
Inhibit 60CTS
60CTS Element
Enabled
Disabled
Inhibit 60CTS
Inhibit 60CTS
VL1
60CTS Vnps
NPS
VL2
V2
Filter
VL3
IL1
60CTS Inps
NPS
IL2
I2
Filter
IL3
Figure 5.4.2-1
Unrestricted Page 80 of 94
A binary input, virtual input or remote data Comms.
&
Logic Diagram: CT Supervision Function (60CTS-I) – 7SR21 & 7SR22
A binary input, virtual input or remote data Comms.
&
<
&
>
Logic Diagram: CT Supervision Function (60CTS) – 7SR22
60CTS-I Delay
&
60CTS Delay
&
©2018 Siemens Protection Devices Limited
60CTS-I Pick-UP
60CTS-I Operated
60CTS-I Operated
60CTS Pick-Up
60CTS Operated
60CTS Operated