Operate And Reset Level; Operate And Reset Time; Voltage Controlled Overcurrent (Ph-Ph); Reference - Siemens Argus 7SR21 Technical Manual

Overcurrent relay
Hide thumbs Also See for Argus 7SR21:
Table of Contents

Advertisement

2.18 51V Voltage Controlled Overcurrent (Ph-Ph)

2.18.1 Reference

Parameter
Vs
Setting
m
Multiplier
Is
Setting

2.18.2 Operate and Reset Level

Attribute
V
Operate level
op
Reset level
Repeatability
Variation

Operate and Reset Time

As per Phase Fault Shaped Characteristic Element (ANSI 51).
Where Pickup Level = Is for Voltage > Vs
Pickup Level = (Is x m) for Voltage < Vs
Unrestricted © 2013 Siemens Protection Devices Limited
Value
5, 5.5...199.5, 200 V
0.25, 0.3...0.95, 1
1 xIn
Value
100 % Vs, ± 1 % or ± 0.25 V
£ 105 % V
± 1 %
£ 5 %
-10 °C to +55 °C
f
- 3 Hz
nom
to f
+ 2 Hz
nom
£ 5 %
harmonics to f
cutoff
7SR21 & 7SR22 Performance Specification
op
Page 47 of 68