4.3 Point List

The information shown below is the default configuration.
4.3.1 Coils (Read Write Binary values)
Address
00001 Binary Output 1
00002 Binary Output 2
00003 Binary Output 3
00004 Binary Output 4
00005 Binary Output 5
00006 Binary Output 6
00007 Binary Output 7
00008 Binary Output 8
00009 Binary Output 9
00010 Binary Output 10
00011 Binary Output 11
00012 Binary Output 12
00013 Binary Output 13
00014 Binary Output 14
00101 Setting G1 selected
00102 Setting G2 selected
00103 Setting G3 selected
00104 Setting G4 selected
00105 Setting G5 selected
00106 Setting G6 selected
00107 Setting G7 selected
00108 Setting G8 selected
00109 CB 1
00112 Auto-reclose active
00113 HotLine Working
00114 E/F Out
00115 SEF Out
00116 Inst Protection Out
00155 Remote Mode
00156 Out Of Service Mode
00157 Local Mode
00158 Local & Remote
00159 Man Override Sync
00160 79 Override Sync
00165 Reset Start Count
00180 CB 1 Opened
00181 CB 1 Closed
00200 User SP Command 1
00201 User SP Command 2
00202 User SP Command 3
00203 User SP Command 4