Mitsubishi Electric Melsec Q Series User Manual page 140

Profibus-dp master module
Hide thumbs Also See for Melsec Q Series:
Table of Contents

Advertisement

4
FUNCTIONS
4
- 31
4.8 Redundant system support function
The following lists the QJ71PB92V errors that may cause system switching.
Table4.9 Errors by Which System Switching Request is Automatically Generated
Error Code
E4E2
H
Hardware failure
E5A1
H
F101
No DP-Slaves are set to perform I/O data exchange in the parameter settings.
H
F10E
Hardware failure
H
*1
Hardware failure or parameter error
F10F
H
F1FF
Hardware failure
H
An error has occurred during processing of system switching (Standby system
FB04
H
Control system)
* 1 Systems are not switched when the power turns OFF and then ON or in Separate mode.
Remark
For details on the error codes, refer to Section 9.5.
Error Description

Advertisement

Table of Contents
loading

Table of Contents