Advertisement

3
SPECIFICATIONS
(4) Input data start address area (for mode 3) (Un\G22784 to Un\G22908)
When the operation mode is Communication mode (mode 3), the start address (buffer
memory address) for each DP-Slave's input data is stored in this area.
Creating a sequence program utilizing the Input data start address area (for mode 3)
(Un\G22784 to Un\G22908) allows address specification of the Input data area
without consideration of the input points for each DP-Slave.
Information of 125 modules is stored in the Input data start address area (for mode 3)
in the same order for each module.
Address
DEC (HEX)
22784(5900
)
Input data start address of 1st module
H
22785(5901
)
Input data start address of 2nd module
H
to
Input data start address of 125th module
22908(597C
)
H
Figure 3.12 Input Data Start Address Area (for mode 3) (Un\G22784 to Un\G22908)
(5) Output data start address area (for mode 3) (Un\G22912 to Un\G23036)
When the operation mode is Communication mode (mode 3), the start address (buffer
memory address) for each DP-Slave's output data is stored in this area.
Creating a sequence program utilizing the Output data start address area (for mode 3)
(Un\G22912 to Un\G23036) allows address specification of the Output data area
without consideration of the output points for each DP-Slave.
Information of 125 modules is stored in the Output data start address area (for mode
3) in the same order for each module.
Address
DEC (HEX)
22912(5980
)
Output data start address of 1st module
H
22913(5981
)
Output data start address of 2nd module
H
to
22036(59FC
)
Output data start address of 125th module
H
Figure 3.13 Output Data Start Address Area (for mode 3) (Un\G22912 to Un\G23036)
22528(5800
22912(5980
3.4 Buffer Memory
3.4.4 I/O data exchange area
b15
The start address (buffer memory address) of the
input data of the 1st module is stored. (Initial value:
FFFF
)
H
)
H
1800
to 27FF
: Input data start address
H
H
FFFF
: Input data not assigned
H
b15
The start address (buffer memory address) of the
output data of the 1st module is stored.
(Initial value: FFFF
)
H
)
H
3800
to 47FF
: Output data start address
H
H
FFFF
: Output data not assigned
H
1
2
b0
3
4
5
b0
6
7
8
3
- 28