Use In Potentially Explosive Atmospheres; Hazardous Atmospheres - ABB 2600T Series Operating Instruction

Multivariable pressure transmitters
Hide thumbs Also See for 2600T Series:
Table of Contents

Advertisement

6
Use in potentially explosive
atmospheres
6.1

Hazardous atmospheres

With or without integrated digital display
Type of protection "Intrinsic Safety"
Approval acc. to ATEX Europa (code E1) and IEC Ex (code E8)
II 1 G Ex ia IIC T6/T5/T4 and
II 1/2 G Ex ia IIC T6/T5/T4; IP67.
II 1 D Ex iaD 20 T85°C and
II 1/2 D Ex iaD 21 T85°C; IP67.
NEPSI China (Code EY)
Ex ia IIC T4~T6, DIP A20T
, T4~T6.
A
Type of protection "Flameproof Enclosure
Approval acc. to ATEX Europa (code E2) and IEC Ex (code E9)
II 1/2 G Ex d IIC T6 and
II 1/2 D Ex tD A21 T85°C (-50 °C ≤ Ta ≤ 75°C); IP67.
NEPSI China (Code EZ)
Ex d IIC T6, DIP A21T
, T6.
A
Type of protection "nL":
ATEX Europa (code E3) and IEC Ex (code ER)
Declaration of Conformity
II 3 G Ex nL IIC T6/T5/T4 and
II 3 D Ex tD A22 T85°C; IP67.
NEPSI China (code EY) Declaration of Conformity
Ex nL IIC T4~T6, DIP A22T
, T6.
A
FM approvals for USA (code E6) and
FM approvals for Canada (code E4):
— Explosion proof (US):
— Explosion proof (Canada): Class I, Div. 1, Groups B, C, D
— Dust Ignition Proof:
— Suitable for:
Class II, Div. 2, Groups F, G; Class III, Div.1, 2
— Non-Incendive:
Class I, Div. 2, Groups A, B, C, D
— Intrinsic Safety: Class I, II, III, Div. 1, Groups A, B, C, D, E, F, G
Class I, Zone 0 AEx ia IIC T6/T4, Zone 0 (FM US)
Class I, Zone 0 Ex ia IIC T6/T4, Zone 0 (FM Canada)
ATEX combined (code EW = E1 + E2 + E3), (code E7 = E1 + E2)
ATEX combined and FM approvals (code EN = EW + E4 + E6)
Combined FM approvals for USA and Canada
— Intrinsic Safety (Code EA)
— Flameproof Enclosure (Code EB)
— Non-incendive (Code EC)
IEC combined (code EH = E8 + E9), (code EI = E8 + E9 + ER)
NEPSI combined (code EP = EY + EZ), (code EQ = EY + EZ + ES)
— GOST (Russia), GOST (Kazakhstan), Inmetro (Brazil) based on ATEX
Class I, Div. 1, Groups A, B, C, D
Class II, Div. 1, Groups E, F, G
For ambient temperatures -40 ... 85°C (-40 ... 185°F) the
information based on the temperature classes in the
associated certificates, must be complied with.
The temperature sensor circuit (Pt100) and the digital output
(pulse / limit value output) must be connected in accordance
with the requirements of the Ex certificate.
WARNING - General danger for Model 266
used in Zone 0!
The housing contains aluminum, which can lead
to a potential danger of ignition through impact or
friction. For this reason, impact or friction must be
avoided during installation and use.
266CRx, 266JRx, 266CSx, 266JSx | OI/266CXX/266JXX/HART-EN Rev. B 11