ABB 2600T Series Operating Instruction page 55

Multivariable pressure transmitters
Hide thumbs Also See for 2600T Series:
Table of Contents

Advertisement

Process Alarm
Calibration
Notice regarding menu "Process Alarm"
In this menu the behavior of the analog output current (current limits) for measuring range overshoots and alarm states can be
configured. As long as the process value moves within the already set span, the output signal is between 4 and 20 mA. If the
process value (PV) underranges the lower range value (LRV), the signal will be set to the configurable lower current limit; if the
process value exceeds the measuring range end URV), the signal will likewise be set to the configurable upper current limit.
If the diagnostic function of the transmitter detects an error, the signal will be set to high alarm or low alarm, depending on the
user-defined setting.
The parameter "Fail Safe Level" (Fail Mode) can be adjusted via the DIP switches 4 and 5 of the electronics module. The precise
value that the signal assumes can be set via the "Process Alarm" menu. In this process the limit for the low alarm current must
be below the lower current limit and the limit for the high alarm current must be above the upper current limit.
Security
Fail Safe Type
Fail Safe Level
Saturation Limits
Process Alarm
Main Pressure Sensor
Output
Reset
Display Unit
Lower Range Value
Upper Range Value
Display Protection
Change Password
Down
Up
Low Saturation
High Saturation
Low Alarm
High Alarm
Low Trimming
High Trimming
Set 4 mA
Set 20 mA
Factory Sensor Trimming
User Sensor Trimming
Factory Output Trimming