LG AR-DR12-05A Installation And Operation Manual page 106

Rooftop dedicated outdoor air system doas vx, base rooftop doas 800 to 5750 cfm, energy recovery wheel rooftop doas 900 to 9550 cfm
Hide thumbs Also See for AR-DR12-05A:
Table of Contents

Advertisement

CONTROLLER
Overview
Table 9: Main Board Analog and Digital Outputs.
Analog Outputs
Drawing Reference
Terminal
7
J4
7
J4
7
J4
7
J4
3
J6
3
J6
Digital Outputs
Drawing Reference
Terminal
15
J12
15
J12
15
J12
15
J13
15
J13
15
J13
15
J14
15
J15
15
J15
15
J16
15
J16
15
J16
15
J17
15
J17
15
J18
15
J18
Chilled water option, no compressors (0 to 10 VDC, direct or reverse).
a
Water source heat pump units only.
b
352 Casing with Active Head Pressure control 2.0.
c
Water source heat pump units with more than one compressor.
d
Units with inverter scroll compressor.
d
Heat pump units.
f
106
Label
Unit Connection
Y1
Modulating compressor output or cooling
capacity output
Y2
Condenser fan VFD output Circ. A; or water
valve output Circ. A
Y3
Hot gas reheat valve output
Y4
Condenser fan VFD output Circ. B
valve output Circ. B
U7
OA/RA damper output
U8
Supply fan speed output
Label
Unit Connection
NO1
Compressor 1 start
NO2
Compressor 2 start
NO3
Compressor 3 start
NO4
Compressor 4 start
NO5
Supply fan start
NO6
Exhaust fan start
NO7
Actuator power
NO8
Global alarm output, BMS output
NO8
Unassigned
NO9
Condenser fan VFD start
NO10
Condenser fan stage 2 start
NO11
Condenser fan stage 3 start
NO12
Unassigned
NC12
Inverter scroll compressor E-stop
NO13
Reversing valve output
NC13
Unassigned
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG" is a registered trademark of LG Corp.
Sensor Type
Use-dependent
a
0–10 Vdc
b
0–10 Vdc
or water
0–10 Vdc
c
d
0–10 Vdc
0–10 Vdc
Position Indicates
Closed = start compressor
Closed = start compressor
Closed = start compressor
Closed = start compressor
Closed = start fan
Closed = start fan
Closed = enabled
Closed = enabled
Closed = start condenser fan
Closed = start condenser fan
Closed = start condenser fan
Open = stop compressor
e
Closed = heating
f
Range
0–100%
0–100%
0–100%
0–100%
0–100%
0–100%

Advertisement