LG AR-DR12-05A Installation And Operation Manual page 137

Rooftop dedicated outdoor air system doas vx, base rooftop doas 800 to 5750 cfm, energy recovery wheel rooftop doas 900 to 9550 cfm
Hide thumbs Also See for AR-DR12-05A:
Table of Contents

Advertisement

Table 27: Network Settings Data Table, continued.
Control Variable
USB Restore
Disable Unit Prior to Restore
Enable Restore
Internal Restore
Disable Unit Prior to Restore
Enable Restore
Last Save Time
IO Status/Offset
Input Offset Ch↑↓
Input Offset
Input Offset Value
Channel Menu IO Type
Channel Menu Ch↑↓
Channel Menu Value
Unit Configuration
Exp 1
Exp 2
Exp 3
Expansion Connection Port
FB2 Expansion Board Baud Rate
FB2 Expansion Board Stop_Bits
FB2 Expansion Board Parity
Airflow Monitoring Density Calc
Supply Fan Control Type
Supply Fan Control K Factor
Exhaust Fan Control Type
Exhaust Fan Control K Factor
Dehumidification Mode Installed
Occupied Dehum. Call Enabled
Unoccupied Dehum. Call Enabled
Unoccupied Unit Operation
Morning Warm Up
Morning Cool Down
Max Duration
Economizer Installed
Econ w/Mech Clg
CO
Control
2
OAD CFM Control
Min OAD CFM Control
Cooling Enabled
Set-point availability varies based on unit configuration.
Default
Min.
Disabled
Disabled
No Restore (□)
No Restore (□)
Disabled
Disabled
No Restore (□)
No Restore (□)
Press Enter to select the analog input channel
Press Enter again to select a value to offset the input by
Current Value of the Channel selected
Select the IO Type: Univ Ch, Digital In, Digital Out, Analog Out
Select the Channel: Dependent on control boards installed
Current Value of the Channel selected
Not Installed
Not Installed
Not Installed
FBus2 to BMS2 FBus2 to BMS2
19200
1200, 2400, 4800, 9600, 19200, 38400, 57600, 76800, 115200
1
1
None
Disabled (□)
Disabled (□)
Constant Volume, Duct Static, Space Static, Hardwired Input, Single
Constant Volume
0.0
0.0
Not Installed, Constant Volume, Space Static, Sup Track w/Off, Pool
Not Installed
Space Static, CFM Control, Hardwired, Rtn Duct Static
0.0
0.0
Disabled (□)
Disabled (□)
Inside RH AND
Inside RH, Inside Dewpoint, Outside Dewpoint, Inside RH OR
Inside
Inside Dewpoint, Inside RH OR Inside Dewpoint OR Outside
Dewpoint OR
Dewpoint, Inside RH AND Inside Dewpoint, Inside RH AND Inside
Outside
Dewpoint
Inside RH, Inside Dewpoint, Inside RH OR Inside Dewpoint,
Inside RH
Night Setback
Night Setback Cycle, Normal Op wUnoc Spts, Recirc wUnoc Spts
Cycle
CMN
Disabled (□)
CMN
Disabled (□)
30 min.
0 min.
CMN
Disabled (□)
Enabled (X)
Disabled (□)
CMN
Not Installed (□)
CMN
Not Installed (□)
CMN
Not Installed (□)
Enabled (X)
Disabled (□)
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG" is a registered trademark of LG Corp.
Network Settings Data Tables
Max.
Enabled
Restore (X)
Enabled
Restore (X)
hh: mm mm/dd/yy
Not Installed, Standard c.pCO, c.pCOe
Not Installed, Standard c.pCO, c.pCOe
Not Installed, Standard c.pCO, c.pCOe
Ethernet IP
2
None, Odd, Even
Enabled (X)
Zone VAV, CFM Control
99999.9
99999.9
Enabled (X)
Dewpoint OR Outside Dewpoint
Inside RH AND Inside Dewpoint
Enabled (X)
Enabled (X)
99 min.
Enabled (X)
Enabled (X)
Installed (X)
Installed (X)
Installed (X)
Enabled (X)
CONTROLLER
Notes
Default determined
by the unit purchased
Default determined
by the unit purchased
137