Alarm Data - LG AR-DR12-05A Installation And Operation Manual

Rooftop dedicated outdoor air system doas vx, base rooftop doas 800 to 5750 cfm, energy recovery wheel rooftop doas 900 to 9550 cfm
Hide thumbs Also See for AR-DR12-05A:
Table of Contents

Advertisement

Table 31: Alarm Data.
Alarm ID
Alarm Screen Line 1
1
Supply Fan 1 Run
2
Fire/Smoke Alarm
3
Phase Protection
4
Freeze Protection
5
High Supply Duct
6
Low Return Duct
7
Outside Air Temp
8
Supply Air Temperature
9 - 10
Cold Coil (x) Temp
11
Exhaust Air Temp
12
HX LA Temperature
13
Mixed Air Temperature
14
Preheat Leaving Temp
15
Return Air Temperature
16
Space Temperature
17
Return Air RH
18
Space RH
19
Supply Air RH
20
HX Leaving RH
21
Outside RH
22 - 23
Cold Coil (x) RH
24
Exhaust Air RH
25
Preheat Leaving RH
26 -29
Low Pressure Switch
30 -33
High Pressure Switch
34
Damper Proving Switch
35
Exhaust Fan 1 Run
36
Return Fan 1 Run
37
Pre-Filters are Dirty
38
OA Filters are Dirty
39
RA Filters are Dirty
40
Cond Drain Pan Full
41 - 44
Exp Board (x) Status
45 - 48
Low Pressure Switch
49 - 52
High Pressure Switch
53 - 64
Belimo Act (x) Comm
65
Non Volatile Memory Er
66 - 68
Supply Fan (x) Run
69 - 71
Exhaust Fan (x) Run
72 - 74
Return Fan (x) Run
75 - 78
Scavenger Fan (x) Run
79
Mixed Air RH
Alarm Screen Line 2
Status Not Proven
In Alarm Position
Relay Tripped
Thermostat Tripped
Static Pressure
Static Pressure
Sensor Value Not Valid
Sensor Value Not Valid
Sensor Value Not Valid
Sensor Value Not Valid
Sensor Value Not Valid
Sensor Value Not Valid
Sensor Value Not Valid
Sensor Value Not Valid
Sensor Value Not Valid
Sensor Value Not Valid
Sensor Value Not Valid
Sensor Value Not Valid
Sensor Value Not Valid
Sensor Value Not Valid
Sensor Value Not Valid
Sensor Value Not Valid
Sensor Value Not Valid
Circuit (x)
Circuit (x)
Dampers are closed
Status Not Proven
Status Not Proven
Replace Filters
Replace Filters
Replace Filters
Check Drain
Board is Offline
Circuit (x)
Circuit (x)
Actuator is Offline
Contact Unison
Status Not Proven
Status Not Proven
Status Not Proven
Status Not Proven
Sensor Value Not Valid
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG" is a registered trademark of LG Corp.
Reset Type
Lockout
Auto
Auto
Auto
Manual
Manual
Manual
Auto
Auto
Auto
Auto
Auto
Auto
Auto
Auto
Auto
Auto
Auto
Auto
Auto
Auto
Auto
Auto
Auto
Auto until Lockout
3x in 1 hr
Auto
Manual
Manual
Manual
Auto
Auto
Auto
Manual
Auto
Auto until Lockout
3x in 1 hr
Auto
Auto
Auto
Manual
Manual
Manual
Manual
Auto
CONTROLLER

Alarm Data

Action Type
Notes
Optional Shutdown Unit
Shutdown Unit
Shutdown Unit
Shutdown Unit
Shutdown Unit
Shutdown Unit
Informational
Shutdown Unit
Disable Cooling Ramp
Disable Defrost
Informational
Informational
Disable Preheat
Disable Return Temp/
Dewpoint Control
Disable Space Temp/
Dewpoint Control
Disable Return RH/
Dewpoint Control
Disable Space RH/
Dewpoint Control
Disable Supply RH/
Dewpoint Control
Informational
Disable OA RH/
Dewpoint Control
Informational
Informational
Informational
Disable Compressor
Circuit
Disable Compressor
Manual at the
Circuit
Switch
Shutdown Unit
Optional Shutdown Unit
Optional Shutdown Unit
Informational
Informational
Informational
Shutdown Unit
Shutdown Unit
Disable Compressor
Circuit
Disable Compressor
Manual at the
Circuit
Switch
Informational
Informational
Optional Shutdown Unit
Optional Shutdown Unit
Optional Shutdown Unit
Optional Shutdown Unit
Informational
141