LG AR-DR12-05A Installation And Operation Manual page 127

Rooftop dedicated outdoor air system doas vx, base rooftop doas 800 to 5750 cfm, energy recovery wheel rooftop doas 900 to 9550 cfm
Hide thumbs Also See for AR-DR12-05A:
Table of Contents

Advertisement

Air Source Heat Pump
Outside Coil Defrost: An air source heat pump periodically needs to initiate a defrost cycle of the outside coil to remove accumulated frost
when operating in heating mode.
Defrost Sequence
1. Initialized: The saturated suction temperature determines when a defrost cycle occurs. For a defrost cycle to initiate, one of the following
must be true:
• The saturated suction temperature is less than set-point; or
• The saturated suction temperature is less than a calculated set-point based on ambient conditions.
At defrost cycle initiation, the following steps occur:
• The reversing valve switches to the cooling position; and
• Condenser fans turn off; and
• The hot gas reheat valve moves to the closed position; and
• Auxiliary heat is enabled.
2. Terminated: The defrost cycle terminates when:
• The saturated suction temperatures of all circuits are greater than or equal to the cancel set-point; or
• The maximum allowed defrost time has been exceeded.
At defrost cycle termination, the unit reverts back to heating mode operation.
3. Auxiliary Heat: Auxiliary heat is enabled with the following constraint: during auxiliary heat, the unit will use heating sources other than
the heat pump in order to maintain the supply air temperature set-point. The electric heat maximum output must meet the auxiliary heat
maximum set-point during defrost.
Controls Lite notifies the third-party controller when auxiliary heat should be enabled.
4. Air Source Heat Pump Heating Lockout: Air source heat pump heating mode is unavailable when:
• The air source heat pump defrost cycle continues for more than the maximum defrost time; or
• A defrost cycle is initiated three (3) times in any one hour period.
• Each strike created by a defrost mode entry clears one hour after the strike occurs.
5. Heating Lockout Reset: The air source heat pump heating lockout resets when:
• The air source heat pump heating lockout occurred more than one hour prior; and
• The outside air temperature increases; or
• The outside humidity decreases.
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG" is a registered trademark of LG Corp.
CONTROLLER
Sequences of Operation
127