Bacnet And Modbus Points - LG AR-DR12-05A Installation And Operation Manual

Rooftop dedicated outdoor air system doas vx, base rooftop doas 800 to 5750 cfm, energy recovery wheel rooftop doas 900 to 9550 cfm
Hide thumbs Also See for AR-DR12-05A:
Table of Contents

Advertisement

BACnet and MODBUS Points

Table 35: BACnet and MODBUS Points List.
Variable
Analog Inputs – Read Only
Cold_Coil_1_Temp_Analog_
Input
Exhaust_Temp_Analog_Input
CL_Coil_Spt_Temp
CL_Supply_Spt_Temp
Mixed_Temp_Analog_Input
Outside_Air_Temp_Analog_
Input
Return_Temp_Analog_Input
Leaving_Water_Temp_1_
Analog_Input
Space_Setpoint_Slider_
Analog_Input
Space_Temp_Analog_Input
Supply_Temp_Analog_Input
Entering_Water_Temp_1_
Analog_Input
Outside_RH_Analog_Input
Return_RH_Analog_Input
Space_RH_Analog_Input
Space_Static_Pressure_
Analog_Input
Supply_Duct_Static_
Pressure_Analog_ Input
Space_CO2_1_Analog_Input
Circuit_A_Discharge_
Pressure_Analog_ Input
Circuit_B_Discharge_
Pressure_Analog_ Input
Exhaust_Fan_Speed_
Analog_Input
Supply_Fan_Speed_Analog_
Input
Entering_Water_Temp_2_
Analog_Input
Leaving_Water_Temp_2_
Analog_Input
Active
Description
Text
Cold Coil 1 Temperature
Exhaust Temperature
Controls Lite Cooling
Coil Set-point
Temperature
Controls Lite Supply Set-
point Temperature
Mixed Temperature
Outside Air Temperature
Return Temperature
Leaving Water
Temperature Circuit A
Space Set-point Slider
Analog Input
Space Temperature
Supply Temperature
Entering Water
Temperature Circuit A
Outside % Relative
Humidity
Return % Relative
Humidity
Space % Relative
Humidity
Space Static Pressure
Supply Duct Static
Pressure
Space 1 CO
ppm
2
Circuit A Discharge
Pressure
Circuit B Discharge
Pressure
Exhaust Fan Speed
Remote Command
Analog Input value
Supply Fan Speed
Remote Command
Analog Input value
Entering Water
Temperature Circuit B
Leaving Water
Temperature Circuit B
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG" is a registered trademark of LG Corp.
BACnet
Inactive
Object
Object
Text
Instance
Type
25
AI
ReadCOV_NoWrite 0.1
30
AI
ReadCOV_NoWrite 0.1
31
AI
ReadCOV_NoWrite 0.1
32
AI
ReadCOV_NoWrite 0.1
35
AI
ReadCOV_NoWrite 0.1
37
AI
ReadCOV_NoWrite 0.1
41
AI
ReadCOV_NoWrite 0.1
42
AI
ReadCOV_NoWrite 0.1
43
AI
ReadCOV_NoWrite 0.1
44
AI
ReadCOV_NoWrite 0.1
45
AI
ReadCOV_NoWrite 0.1
46
AI
ReadCOV_NoWrite 0.1
86
AI
ReadCOV_NoWrite 0.1
88
AI
ReadCOV_NoWrite 0.1
89
AI
ReadCOV_NoWrite 0.1
94
AI
ReadCOV_NoWrite 0.001 30366
95
AI
ReadCOV_NoWrite 0.01 30368
116
AI
ReadCOV_NoWrite
119
AI
ReadCOV_NoWrite 0.1
121
AI
ReadCOV_NoWrite
143
AI
ReadCOV_NoWrite
155
AI
ReadCOV_NoWrite
161
AI
ReadCOV_NoWrite 0.1
162
AI
ReadCOV_NoWrite 0.1
CONTROLLER
BACnet and MODBUS Points
Access
Hyst Index
30244
30254
30256
30258
30264
30268
30276
30278
30280
30282
30284
30286
30350
30354
30356
10
30402
30408
1
30412
1
30456
1
30462
30468
30470
MODBUS
Register
Size
Type
Input
2
Input
2
Input
2
Input
2
Input
2
Input
2
Input
2
Input
2
Input
2
Input
2
Input
2
Input
2
Input
2
Input
2
Input
2
Input
2
Input
2
Input
2
Input
2
Input
2
Input
2
Input
2
Input
2
Input
2
145