CONTROLLER
Network Settings Data Tables
Table 30: Network Settings Data Table - Alarm Management.
Control Variable
Shutdown Alarms
Supply High Static Alarm Set-point
Supply Temp. Low Limit Alarm Set-point
Supply Temp. Low Limit Delay
Supply Temp. High Limit Alarm Set-point
Supply Temp. High Limit Delay
Space High Static Alarm Set-point
Shutdown Alarm Lockout Enable
Supply Fan Alarm Shutdown Unit
Exhaust Fan Alarm Shutdown Unit
General Alarms
Alarm Digital Output Type
Low Saturated Suction Temperature
Fan Alarm Delay
Internal Board Temp.
Set-point availability varies based on unit configuration.
140
Default
4.000"wc
35.0°F
5 min.
120.0°F
3 min.
0.200"wc
Enabled (X)
Enabled (X)
Enabled (X)
Any Alarm
25.0°F
60 sec.
Enabled (X)
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG" is a registered trademark of LG Corp.
Min.
Max.
0.000"wc
5.000"wc
30.0°F
50.0°F
0 min.
15 min.
90.0°F
120.0°F
0 min.
15 min.
-0.500"wc
0.500"wc
Disabled (□)
Enabled (X)
Disabled (□)
Enabled (X)
Disabled (□)
Enabled (X)
Shutdown
Any Alarm
0.0°F
40.0°F
30 sec.
120 sec.
Disabled (□)
Enabled (X)
Notes
WSHP Only