CONTROLLER
Set-Points Data Tables
Table 21: Energy Recovery Set-Points Data Table.
Control Variable
Defrost Ramp Exhaust Set-point
Heat Wheel
Minimum Speed
Enable Jog
Jog Enable Delay
Jog Duration
Table 22: Fan Control Set-Points Data Table.
Control Variable
Supply Fan Control
Enable Delay
Minimum Speed
Maximum Speed
Constant Volume Set-point
Occupied
Unoccupied
Duct Static Set-point
Space Static Set-point
Airflow Set-point
Soft Shutdown Enable
Set-point
Delay
Exhaust Fan Control
Constant Volume Set-point Enable Delay
Constant Volume Set-point Enable When OAD
>=
Minimum Speed
Maximum Speed
Constant Volume Set-point Occupied
Constant Volume Set-point Unoccupied
Space Static Set-point
Supply Tracking Offset
Airflow Set-point
132
Default
36.0°F
20%
Enabled (X)
60 min.
2 min.
Default
5 sec.
50%
100%
100%
60%
1.00"wc
0.05"wc
0 CFM
85.0°F
120 sec.
0 sec.
15%
25%
100%
100%
60%
0.05"wc
-10%
0 CFM
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG" is a registered trademark of LG Corp.
Min.
Max.
15.0°F
50.0°F
0%
100%
Disabled (□)
Enabled (X)
10 min.
300 min.
1 min.
99 min.
Min.
Max.
0 sec.
60 sec.
50%
100%
50%
100%
50%
100%
50%
100%
0.00"wc
5.00"wc
-0.50"wc
0.50"wc
0 CFM
999999 CFM
70.0°F
150.0°F
0 sec.
999 sec.
0 sec.
60 sec.
0%
99%
25%
100%
25%
100%
25%
100%
25%
100%
-0.50"wc
0.50"wc
-100%
100%
0 CFM
999999 cfmCFM