Table 25: Advanced Set-Points Data Table, continued.
Control Variable
Advanced Set-points, continued.
Temp Reset PID Tuning P Gain
Temp Reset PID I Time
Temp Reset PID Cycle Time
Cooling/HP PID Tuning P Gain
Cooling/HP PID Tuning I Time
Cooling/HP PID Tuning Cycle Time
Cooling/HP PID Tuning Deadband
Heating PID Tuning P Gain
Heating PID Tuning I Time
Heating PID Tuning Cycle Time
Heating PID Tuning Deadband
Supply Duct Static PID P Gain
Supply Duct Static PID I Time
Supply Space Static PI P Gain
Supply Space Static I Time
Return Static PID P Gain
Return Static PID I Time
Winter Ramp PID Tuning P Gain
Winter Ramp PID Tuning I Time
Winter Ramp PID Tuning Cycle Time
Winter Ramp PID Tuning Deadband
OAD Airflow Ramp P Gain
OAD Airflow Ramp I Time
Min OAD Airflow Ramp P Gain
Min OAD Airflow Ramp I Time
Heat Wheel Bypass P Gain
Heat Wheel Bypass I Time
Circuit Pressure P Gain
Circuit Pressure I Time
Economizer P Gain
Economizer I Time
Economizer Disable Fallback
Hot Gas Reheat P Gain
Hot Gas Reheat I Time
CO
Control P Gain
2
CO
Control I Time
2
Supply Fan Airflow P Gain
Supply Fan Airflow I Time
Exhaust Fan Airflow P Gain
Exhaust Fan Airflow I Time
HGRH Purge Mode Purge Interval
HGRH Purge Mode Purge Duration
Login Duration
Chilled Water Valve Position
Modulating Compressor Minimum Signal
Cooling
Modulating Compressor Minimum Signal
Dehumidify
Comp Signal Ramp Rate
Password Management - Service Password
WSHP Freeze Protection
WSHP Compressor Delay
Set-point availability varies based on unit configuration.
Default
6.000
300 sec.
30 sec.
3.000
60 sec.
1 sec.
0.0
3.000
150 sec.
1 sec.
0.0
4.000
30 sec.
100.000
30 sec.
0.500
60 sec.
1.000
200 sec.
1 sec.
1.0°F
0.015
30 sec.
0.020
250 sec.
2.000
60 sec.
1.800
20 sec.
2.000
300 sec.
Disabled (□)
10.000
150 sec.
4.000
600 sec.
0.006
40 sec.
0.006
40 sec.
60 min.
120 sec.
30 min.
Closed
12%
50%
30 sec.
9998
0.0°F
60 sec.
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG" is a registered trademark of LG Corp.
CONTROLLER
Set-Points Data Tables
Min.
Max.
0.001
999.999
0 sec.
1800 sec.
0 sec.
100 sec.
0.001
999.999
0 sec.
1800 sec.
0 sec.
100 sec.
0.0
10.0
0.001
999.999
0 sec.
1800 sec.
0 sec.
100 sec.
0.0
10.0
0.001
999.999
0 sec.
1800 sec.
0.001
999.999
0 sec.
1800 sec.
0.001
999.999
0 sec.
1800 sec.
0.001
999.999
0 sec.
1800 sec.
0 sec.
100 sec.
0.0°F
50.0°F
0.001
999.999
0 sec.
1800 sec.
0.001
999.999
0 sec.
1800 sec.
0.001
999.999
0 sec.
1800 sec.
0.001
999.999
0 sec.
1800 sec.
0.001
999.999
0 sec.
1800 sec.
Disabled (□)
Enabled (X)
0.001
999.999
0 sec.
1800 sec.
0.001
999.999
0 sec.
1800 sec.
0.001
999.999
0 sec.
1800 sec.
0.001
999.999
0 sec.
1800 sec.
30 min.
480 min.
45 sec.
300 sec.
5 min.
60 min.
Closed
Open
12%
100%
Cooling Min.
100%
1 sec.
100 sec.
0001
9999
32.0°F
32.0°F
30 sec.
120 sec.
Notes