LG AR-DR12-05A Installation And Operation Manual page 152

Rooftop dedicated outdoor air system doas vx, base rooftop doas 800 to 5750 cfm, energy recovery wheel rooftop doas 900 to 9550 cfm
Hide thumbs Also See for AR-DR12-05A:
Table of Contents

Advertisement

CONTROLLER
BACnet and MODBUS Points
Table 42: BACnet and MODBUS Points List, continued.
Variable
Binary Values – Read Only, continued.
Allow_Dampers
Allow_Exhaust_Fans
Allow_Supply_Fans
BMS_Watchdog_Active
BMS_Occupancy_Status
Cond_Water_Pump_
Required
Damper_Actuator_Power_1_
Digital_Output
Compressor_1_Enable_
Digital_Output
Compressor_2_Enable_
Digital_Output
Compressor_3_Enable_
Digital_Output
Compressor_4_Enable_
Digital_Output
Condenser_Fan_1_Digital_
Output
Condenser_Fan_2_Digital_
Output
Condenser_Fan_3_Digital_
Output
Exhaust_Fan_1_Start_Stop_
Digital_Output
Furnace_1_Stage_1_Digital_
Output
Furnace_2_Stage_1_Digital_
Output
Heat_Wheel_Enable_Digital_
Output
PreHeat_Enable_Digial_
Output
Reversing_Valve_Digital_
Output
Supply_Fan_1_Start_Stop_
Digital_Output
Bacnet_License_not_
Installed_Alarm. Active
BMS_Offline_Alarm.Active
Cold_Coil_1_Temperature_
Sensor_Alarm. Active
152
Active
Description
Text
Startup sequence
command to open
Yes
dampers
Startup sequence
command to trigger
Yes
exhaust fans to start
Startup sequence
command to trigger
Yes
supply fans to start
Status of the BMS
Active
watchdog ping
Status of the BMS
Unoccupied Occupied
occupancy command
WSHP Water Pump
On
Requested
Damper Actuator
Power 1 Digital
Active
Output
Compressor 1 Enable
On
Compressor 2 Enable
On
Compressor 3 Enable
On
Compressor 4 Enable
On
Condenser Fan
On
Stage 1
Condenser Fan
On
Stage 2
Condenser Fan
On
Stage 3
Exhaust Fan 1 Start
On
Stop
Furnace 1 Stage 1
On
Furnace 2 Stage 1
On
Heat Wheel Enable
On
PreHeat Enable
On
Digital Output
Reversing Valve
Heating
Supply Fan 1 Start
Start
Bacnet License not
Alarm
Installed Alarm
BMS Offline Alarm
Alarm
Cold Coil 1
Temperature Sensor
Alarm
Alarm
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG" is a registered trademark of LG Corp.
BACnet
Inactive
Object
Object
Text
Instance
Type
No
43
BV
ReadCOV_NoWrite
No
44
BV
ReadCOV_NoWrite
No
48
BV
ReadCOV_NoWrite
Inactive
49
BV
ReadCOV_NoWrite
50
BV
ReadCOV_NoWrite
Off
60
BV
ReadCOV_NoWrite
Inactive
100
BV
ReadCOV_NoWrite
Off
111
BV
ReadCOV_NoWrite
Off
112
BV
ReadCOV_NoWrite
Off
113
BV
ReadCOV_NoWrite
Off
114
BV
ReadCOV_NoWrite
Off
119
BV
ReadCOV_NoWrite
Off
120
BV
ReadCOV_NoWrite
Off
121
BV
ReadCOV_NoWrite
Off
127
BV
ReadCOV_NoWrite
Off
131
BV
ReadCOV_NoWrite
Off
133
BV
ReadCOV_NoWrite
Off
163
BV
ReadCOV_NoWrite
Off
166
BV
ReadCOV_NoWrite
Cooling
175
BV
ReadCOV_NoWrite
Stop
186
BV
ReadCOV_NoWrite
Normal
300
BV
ReadCOV_NoWrite
Normal
313
BV
ReadCOV_NoWrite
Normal
387
BV
ReadCOV_NoWrite
MODBUS
Register
Access
Hyst Index
0
10029 Discrete
0
10030 Discrete
0
10034 Discrete
0
10035 Discrete
0
10036 Discrete
0
10042 Discrete
0
10153 Discrete
0
10164 Discrete
0
10165 Discrete
0
10166 Discrete
0
10167 Discrete
0
10172 Discrete
0
10173 Discrete
0
10174 Discrete
0
10180 Discrete
0
10184 Discrete
0
10186 Discrete
0
10208 Discrete
0
10211 Discrete
0
10220 Discrete
0
10231 Discrete
0
10251 Discrete
0
10264 Discrete
0
10338 Discrete
Size
Type