Change the Windows Computer Name in the Server Node
14. Now change the Windows Computer Name and if needed the IP address of the
computer. Remember to update the Host file (in both server and clients).
("C:\WINDOWS\system32\drivers\etc\hosts").
15. The server address for the license system has to be adjusted. To do this open
START>All Programs>ABB Industrial IT Base>System>Licensing>License
Status Viewer.
16. Select Tools>Change CLS Machine, to get the dialog below.
Figure 80. Change CLS Machine
17. Enter the new name e.g. "HMI-Server55" and press Apply and exit the License
Status Viewer.
18. Restart the computer and log in as SysAdmin.
19. If you are using the AC 800M OPC server, open the OPC server configuration
dialog and disconnect and connect each of the controllers once. After this save
the configuration.
20. If you are setting up an autonomous redundant backup system (otherwise skip
this step) please copy the backup files from the main system server (typically
from folder located on "Backup Disc:\Backup" in the server workplace) to the
backup system server (same location).
21. Open the Configuration Wizard and select Restore System and click Next.
130
Section 7 Administration
3BSE040587R4401