CABLES & FUSES
Cable sections and fuse ratings recommended according to (IEC 60950-1)
Alternatively, local standards to be respected!
RATINGS
SINGLE INPUT FEED
Input fuse A-Type: gL or CB
Input cable A
Output cable D
Battery fuse E-Type: gR or CB
Battery cable E
DUAL INPUT FEED
Input fuse B-Type: gL or CB
Input Cable B
Input fuse C-Type: gR or CB
Input cable C
Output cable D
Battery fuse E-Type: gR or CB
Battery cable E
PowerValue 11/31 T Technical Specifications
 
10 kVA (1-1)
10 kVA (3-1)
1 x 63A
3 x 63A
3 x 16mm
2
5 x 16mm
3 x 16mm
2
3 x 16mm
2 x 40A
2 x 40A
3 x 6mm
2
3 x 6mm
1 x 63A
3 x 25A
3 x 16mm
2
5 x 4mm
1 x 63A
1 x 63A
3 x 16mm
2
3 x 16mm
3 x 16mm
2
3 x 16mm
2 x 40A
2 x 40A
3 x 6mm
2
3 x 6mm
 
20 kVA (1-1)
1 x 100A
2
3 x 25mm
2
3 x 25mm
2 x 80A
2
3 x 16mm
1 x 100A
2
3 x 25mm
1 x 100A
2
3 x 25mm
2
3 x 25mm
2 x 80A
2
3 x 16mm
Page 12
20 kVA (3-1)
3 x 100A
2
5 x 25mm
2
3 x 25mm
2 x 80A
2
3 x 16mm
3 x 50A
2
5 x 10mm
1 x 100A
2
3 x 25mm
2
3 x 25mm
2 x 80A
2
3 x 16mm
2
2
2
2
2
2
2
 