Technical Specifications
This section provides important technical specifications related to the device.
5.1
Power Supply Specifications
Note
When determining cable lengths, make sure the minimum input voltage for the pow-
er supply is provided at the power source.
a
Power consumption varies based on the device configuration.
5.2
Failsafe Relay Specifications
Maximum Switching Voltage
5.3
Operating Environment
The RUGGEDCOM RX1512 is rated to operate under the following environmental
conditions.
NOTICE
Temperature limits for select line modules may differ from that which can be with-
stood by the RUGGEDCOM RX1512. Make sure the selected modules are rated for
the expected environmental conditions before deployment. For more information,
refer to the RUGGEDCOM RX1512 Series Modules Catalog.
Ambient Operating Tempera-
ture
Ambient Storage Temperature -40 to 85 °C (-40 to 185 °F)
RUGGEDCOM RX1512
Installation Manual, 07/2019, C79000-G8976-1057
Power Sup-
ply Type
Min
Internal
11 VDC
30 VDC
125 VDC
125 VAC
220 VDC
250 VAC
a b c
Input Range
Max
72 VDC
Rated Switching Current
2 A, 60 W
0.24 A, 30 W
0.5 A, 62.5 W
0.24 A, 60 W
0.25 A, 62.5 W
-40 to 85 °C (-40 to 185 °F)
Internal
Maximum Power
Fuse Rating
Consumption
6.3 A
26.4 W
Isolation
1500 V
for 1 minute be-
rms
tween coil and contacts
5
a
33