Certification

6.1.7 Other Approvals

6.1.7
Other Approvals
This device meets the requirements of the following additional standards:
6.2

EMC and Environmental Type Tests

The RUGGEDCOM RX1512 has passed the following Electromagnetic Compatibility
(EMC) and environmental tests.
EMC Type Test for IEC 61850-3
IEC 61000-4-2
IEC 61000-4-3
IEC 61000-4-4
IEC 61000-4-5
IEC 61000-4-6
IEC 61000-4-8
IEC 61000-4-12
IEC 61000-4-16
40
IEEE 1613
IEEE Standard Environmental and Testing Requirements for Communications
Networking Devices in Electric Power Substations
IEC 61000-6-2
Electromagnetic Compatibility (EMC) – Part 6-2: Generic Standards – Immunity
for Industrial Environments
IEC 61850-3
Communication Networks and Systems in Substations – Part 3: General Require-
ments
Test
ESD
Radiated RFI
Burst (Fast Transient)
Surge
Induced (Con-
ducted) RFI
Magnetic Field
Damped Oscillatory
Mains Frequen-
cy Voltage
Description
Enclosure Contact
Enclosure Air
Enclosure Ports
Signal ports
DC Power Ports
Earth ground ports
Signal ports
DC Power Ports
Signal ports
DC Power Ports
Earth ground ports
Enclosure Ports
Signal ports
DC Power Ports
Signal ports
DC Power Ports
Test Levels
± 8 kV
± 15 kV
20 V/m
± 4 kV @ 2.5 kHz
± 4 kV
± 2 kV Line-to-Ground
± 2 kV Line-to-Line
± 2 kV Line-to-Ground
± 1 kV Line-to-Line
10 V
100 A/m, continuous
1000 A/m for 1 s
1000 A/m for 1 s
2.5 kV common, 1 kV dif-
ferential mode @1 MHz
30 V Continuous
300 V for 1 s
RUGGEDCOM RX1512
Installation Manual, 07/2019, C79000-G8976-1057
Severity
Levels
4
a
Note
4
4
3
3
a
Note
5
3
4