FusionModule2000 Smart Modular Data Center
Maintenance Guide
Item

3.5 Semiannual Maintenance

Table 3-8 Semiannual maintenance for the power supply and distribution system
Item
UPS cleanliness
Oxidation of metal
components in the
PDC or new main
way
Table 3-9 Semiannual maintenance for the cooling system
Item
Temperature and
humidity sensor
calibration
Evaporator
appearance
Issue 04 (2020-01-03)
Operation
the WebUI of
the ECC800.
Operation
Visual observation
Visual observation
Operation
Use a high-precision
temperature and
humidity sensor to
calibrate the
temperature and
humidity sensors
inside and outside
the cabinet.
Visual observation
Copyright © Huawei Technologies Co., Ltd.
Standard
Standard
The white paper that
you use to wipe the
panels is clean.
No metal component
rusts.
Standard
The temperature
deviation is lower
than 1° C or
humidity deviation
is lower than 5%.
The evaporator fins
are not pushed
down.
3 Routine Maintenance
Troubleshooting
status sensor.
Troubleshooting
If the white paper
becomes dirty, clean
up the dust,
especially from the
air filter on the front
door, or replace the
air filter.
If any metal
component
suffers from
severe oxidation,
remove the rust
or replace the
component in a
timely manner.
If the component
is painted,
repaint it after
removing the
rust.
Troubleshooting
If the temperature
deviation is greater
than 1° C or
humidity deviation
is greater than 5%,
the T/H sensor must
be calibrated or
replaced.
Use a fin brush to
organize the fins that
are pushed down.
30