Figure 5-41 Electronic lock
Step 3 Install a new electronic lock and connect the monitoring cable to the new lock.
Step 4 Log in to the ECC800 WebUI and choose System Settings > Access Management. Set the
access permission for the new electronic lock according to the access permission setting for
the faulty electronic lock. Then perform the Synchronize to Device operation.
Step 5 On the ECC800 WebUI, choose Monitoring > System > ECC800 > Controls > Delete
device with communication failure, and click Submit.
Step 6 Check that the electronic lock functions properly.
----End
5.4.4 Parts Replacement for the Intelligent Battery Monitoring
System

5.4.4.1 Replacing an iBOX

Impact on the System
The battery data cannot be monitored.
Preparations
Procedure
Step 1 Clear the network parameters for all the iBATs managed by the iBOX to be replaced.
Issue 04 (2020-01-03)
Material: iBOX
Skill requirement: hardware installation engineers
Copyright © Huawei Technologies Co., Ltd.
5 Parts Replacement