Huawei FusionModule2000 V500R003C10 Maintenance Manual page 45

Smart modular data center
Hide thumbs Also See for FusionModule2000 V500R003C10:
Table of Contents

Advertisement

FusionModule2000 Smart Modular Data Center
Maintenance Guide
Item
PDC air-tightness
Dust on the skylight
tempered glass,
batteries, in the
PDC, and on the
new main way
Appearance of
structures such as
aisle end doors and
skylights
Issue 04 (2020-01-03)
Operation
threshold, to refresh
the capacity of the
battery.
Visual observation
Visual observation
Visual observation
Copyright © Huawei Technologies Co., Ltd.
Standard
Check cable holes
and PDC sealing
plates, there is no
hole, and sealing
plates have not
shifted.
There is no dust or
foreign matter.
Structures such as
aisle end doors and
skylights are free
from deformation,
corrosion, and paint
flake-off.
3 Routine Maintenance
Troubleshooting
2. If the fault
persists, contact
Huawei technical
support.
If there is a hole or a
sealing plate has
shifted, seal the
cable hole or
reinstall the sealing
plate.
Clean with a soft
cotton cloth.
Replace a
component if its
function is affected.
38