Localize With Device Identification - Siemens Cerberus CS1140 Commissioning

Fire detection system
Hide thumbs Also See for Cerberus CS1140:
Table of Contents

Advertisement

4.3.4

Localize with device identification

Requirements
Enter ID number, type and installation location of the first detector on the com-
missioning list or ground plan
Insert detector into the base
Repeat the procedure until all required detectors have been localized
Fire & Security Products
Siemens Building Technologies Group
Automatic detectors:
Detector bases installed
Detectors not inserted
ÕThis localization method is possible in a currentless state; the control unit
must not, therefore, be installed. It is useful when a detector must be installed
in areas which will later become inaccessible.
Note:
The data (identification numbers, detector types, bus addresses) of the detectors local-
ized by device identification must also be read into the control unit. If address allocation is
carried out at a later time, data from all existing devices are read in after switching to ad-
dress allocation mode, i.e. including from those devices localized by device identification.
If no address allocations are carried out, these data may be read in in the following way:
Switch line to 'address allocation through activation' or 'through insertion' and wait until
the mode becomes active (Õ pages 91/93)
ÕThe device data are read in
Deactivate address allocation (Õ page 93)
Õthe data, which are now localized in the control unit, can be loaded using the function
Comm Õ Fast Upload Loc. –> PC in the SWE11 (Õ Page 94)
Identification number
(device identification)
8038
4790
5
laboratory 201
4
2
3
laboratory 203
1
80384790
laboratory 205
office
office office
8
202
204
206
corridor 200
10
9
7
office
office
office
6
207
209
211
31
e1249d 2
01.1999