Siemens Cerberus CS1140 Commissioning page 66

Fire detection system
Hide thumbs Also See for Cerberus CS1140:
Table of Contents

Advertisement

62
Fire & Security Products
Siemens Building Technologies Group
DC1136 as input element (output section not used)
ü
Use only in exceptional circumstances!
Even if only the input section of the module is used, it still occupies two D-Bus addresses.
In the physical structure, an output section (DC1136o) and an input section (DC1136i)
must be created but only the output section (DC1136o) is linked to the logical structure.
The output section always occupies the lower D-Bus address in this case too.
e1249d 3
01.1999