Fujitsu FLM 150 ADM Maintenance And Trouble Clearing page 111

Table of Contents

Advertisement

Maintenance and Trouble Clearing
FJTU-320-515-480
4.6.2
Procedure
Step 1
If you have a known-good unit, use it to replace the SV1A unit, or locate another
unit and inspect it for damage, debris, and foreign objects. Verify that you have
the correct type of SV1A unit for your application:
SV1A-TL1 with the MP1A supports TL1/FLEXR
low-speed DS1 facility types only. Refer to Figure 4-10.
SV1A-TL2 with the MP1A-V2 supports TL1/FLEXR interfaces and all
middle-speed and low-speed options. Refer to Figure 4-11.
SV1A-TL3 with the MP1A-V2 (Issue 06) supports TL1, FLEXR, and Menu
Mode interfaces and all middle-speed and low-speed options. Refer to
Figure 4-11.
SV1A-TL4 with MP1A-V3 supports TL1/FLEXR, and all middle-speed
and low-speed options, as well as supporting the OC-12 high-speed
interface and the TS1A-ENH unit. Refer to Figure 4-11.
SV1A-R11 with MP1A-R11 supports TL1/FLEXR, and all middle-speed
and low-speed options, as well as supporting the OC-12 high-speed
interface and the TS1A-ENH unit. Refer to Figure 4-11.
SV1A-TDL1 supports all middle-speed, low-speed, and high-speed options
and the TS1A-ENH/-ENH2, EC1A-DL1/-DL2, and transmux units. Refer
to Figure 4-12.
SV1A-TB with the MP1A-V2 supports TL1, FLEXR, and telemetry
byte-oriented serial (TBOS) protocol interfaces and all middle-speed and
low-speed options. Refer to Figure 4-13.
Step 2
Set the option switches to the same positions as those used on the removed unit.
Note: The SV1A-TB does not have option switches.
Step 3
Replace the original unit. Is the FAIL LED on the SV1A unit off?
Complete your fault-reporting documentation.
You have completed this procedure.
Issue 9, May 1999
If Yes:
FNC and FNC Customer Use Only
4.6: Replacing the Supervisory (SV1A) Unit
®
interfaces and
If No:
Go to Step 4.
Vol. ll, Page 480.4-19

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents