Huawei FusionModule1000A40 Commissioning Manual page 55

Prefabricated all-in-one data center
Hide thumbs Also See for FusionModule1000A40:
Table of Contents

Advertisement

FusionModule1000A40 Prefabricated All-in-One Data
Center
Commissioning Guide
Figure 8-3 MDU front view
(1) Alarm indicator
Table 8-2
Table 8-2 Alarm indicator status
Status
On
Off
Figure 8-4
Issue 04 (2020-01-17)
describes the alarm indicator status.
Color
Meaning
Red
A critical alarm is generated for the integrated UPS, and the
buzzer buzzes.
Yellow
A major alarm has been generated for the integrated UPS, and
the buzzer buzzes at an interval of 0.5s.
A warning has been generated for the integrated UPS, or the
Green
system is running properly.
N/A
The LCD of the integrated UPS has experienced a power
failure.
shows the MDU ports.