FusionModule1000A40 Prefabricated All-in-One Data
Center
Commissioning Guide
Figure 8-12 Teamwork settings screen 4
Table 8-5 Teamwork setting description
Parameter
Description
Teamwork
Group the smart cooling products in
unit no.
adjacent areas as one, that is, assign
one teamwork control number for
them. At most four teamwork control
groups can be assigned (1–4).
Teamwork
Indicates the address (1 to 32) of a
unit address
smart cooling product in a group.
Teamwork
Indicates whether to disable or enable
function
the teamwork function.
Disable: A unit operates
independently.
Enable, a unit operates in team
with other units.
Teamwork
Set the teamwork working mode. The
mode
options include smart and iCooling.
Issue 04 (2020-01-17)
Configuration Principle
Set the assigned teamwork control
number.
Set this parameter based on the onsite
device heat distribution.
Determine whether to enable the
iCooling mode based on onsite heat
load variations. If the heat load varies
greatly, it is recommended that you
enable the iCooling mode. The
Copyright © Huawei Technologies Co., Ltd.
8 Commissioning Core Components
Addresses in the same group must
be unique, and the address of the
master unit must be set to 1.
Set the value to an integer in the
range from 1 to the number of
devices in the current group. If the
address of a device exceeds the
range, the device cannot enter the
teamwork group.
If an address in the range is not
configured, the teamwork topology
shows that this device is offline.
Default
Value
1
NA
Disable
smart
60