Checking The Installation - Huawei OptiX OSN 2500 Quick Installation Manual

Hide thumbs Also See for OptiX OSN 2500:
Table of Contents

Advertisement

Checking the Installation

1
Checking Installation Effectiveness
No.
1
The cabinet is installed in the position specified in the engineering design documents.
The mechanical parts of the cabinet are installed correctly and securely, and are not
2
damaged. The surfaces of the cabinet do not contain any fingerprints, stains, or scratches.
3
The cable holes on the top and at the bottom of the cabinet are sealed properly.
4
The cables are routed according to the engineering design documents.
The cables are not damaged or broken and do not contain any joints. The cable connectors
5
are connected correctly and securely.
6
The labels at both ends of the cables and optical fibers are correct, legible, and in good order.
The optical fibers outside the cabinet are not pinched or pressed by other cables or articles
7
and are placed in a protective corrugated tube or cable trough.
The bending radius of the optical fibers is not less than 40 mm. No protruding component
8
exists on the routing path of the optical fibers.
The optical fibers are properly arranged and bound with binding straps and do not contain any
9
scratches.
2
Checking Equipment Prior to Powering Up
Ensure that fixed optical attenuators have been configured as required, before powering on the subrack.
Ensure that the circuit breaker corresponding to the idle power cable is in the "OFF" state, before powering on
the equipment
Turn off the power supply facilities, and then measure the resistance between NEG(-), RTN(+), and PGND using a
multimeter.
Circuit Breaker
Turn all the power switches on the DC
power distribution box to "OFF―.
Turn all the power switches on the DC
power distribution box to "ON―.
Turn off all the power switches after the measurement.
What to Check For
Resistance Between
Resistance Between
NEG(-) and RTN(+)
NEG(-) and PGND
More than 20,000 ohms
More than 20,000 ohms
51
Method
Check the
position.
Check.
Check.
Check.
Check.
Check.
Check.
Check.
Check.
Resistance Between
RTN(+) and PGND
0