Ventilation,
Master controller RMU
Heating,
Slave controller, RMH
Note
Zone addressing
Heating setpoints
Building Technologies
HVAC Products
The ventilation settings for an RMU master controller programmed with plant type
A03 (ADC001 MU1 HQ) are carried out under:
...> Commissioning > Communication > Room
Geogr zone (Apart): 3
...> Commissioning > Settings > Controller 1 > Cascade controller
Control strategy: Alternating
The heating settings for an RMH slave controller programmed with basic type 0-2
are carried out under:
...> Commissioning > Communication > Room 1
Geogr zone (apart): 3
...> Commissioning > Extra configuration > Heating circuit 1 > Functions
Room control combination: Ext. setpoint (slave, internal setpoint
...> Commissioning > Extra configuration > Heating circuit 1 > Optimizations/Influences
Room temperature influence 0
If the same room is controlled by an RMU ventilation controller and an RMH
heating controller, the RMU ventilation controller in this room control combination
must be set to "Master".
QAW740
Room unit
Geogr zone = 3
The heating setpoints
Comfort heating setpoint
Precomfort heating setpoint
Economy heating setpoint
are transmitted by the ventilation controller to the heating controller over the KNX
bus. The existing setpoints heating controller are overwritten.
Both controllers then operate with the same heating setpoint. If a heating controller
setpoint needs to be adjusted, it must be changed in the ventilation controller
(master).
Basic documentation: Communication via the KNX bus
Appendix
RMU...
Room operating mode
Ventilation 1
Geogr zone = 3
Room control comb. =
Master
RMH...
Room operating mode
Heating circuit 1
Geogr zone = 3
Room control comb. =
Slave ext. setpoints
103/120
CE1P3127en
30.08.2007