58/120
Building Technologies
HVAC Products
7. In ACS Service click Plant > Refresh device list to initiate the automatic adoption of
the new line address 11 by the Synco devices.
8. In ACS Service select Plant > Edit device list... to open the "Edit device list" dialog
box.
9. Check that the Synco devices are now using the new line address 11.
5.9.2

Area couplers

The area address (syntax A.0.0 from 1.0.0 to 15.0.0) can be set in "Programming
mode" via ACS Service in the same way as for the line coupler.
In principle the method is the same as for the line coupler (see Steps 1 to 9 above).
Note:
• Area couplers are always the highest-level elements in a network. Area
addresses can never be adopted automatically.
• For area couplers, the line address and device address is always 0.
Basic documentation: Communication via the KNX bus
Device addresses via ACS
CE1P3127en
30.08.2007