Building Technologies
HVAC Products
6
Basic communication settings
6.1
RM... controllers
6.1.1
Decentral bus power
The type of bus power supply is set on the "Basic settings" operating page, on the
"Decentral bus power supply" line.
Main menu > Commissioning > Communication > Basic settings
Basic settings
Device address:
Dec bus power supp:
Clock time op:
Rem set clock save:
Decentral bus power supply, RM... controllers
Default.
On
Settings
Off / On
In small networks the KNX bus can be operated with the default value "Dec bus
power supp: On". Refer to section 2.2 for information about the bus power supply.
6.1.2
Clock time operation
"Clock time operation" refers to the transmission of the date and time. For the
RM... controllers, this is set on the "Clock time op:" line of the "Basic settings"
operating page.
Main menu > Commissioning > Communication > Basic settings
Basic settings
Device address:
Dec bus power supp:
Clock time op:
Rem set clock save:
Basic settings
Device address:
Dec bus power supp:
Clock time op:
Rem set clock save:
Basic settings
Device address:
Dec bus power supp:
Clock time op:
Rem set clock save:
Clock time mode, RM... controllers
Default.
Master
Settings
Autonom. / Slave / Master.
Basic documentation: Communication via the KNX bus
Basic communication settings
10
On
Master
Yes
10
On
Master
Yes
10
On
Slave
Yes
10
On
Autonom
Yes
61/120
CE1P3127en