Device Address - Siemens Synco 700 Series Basic Documentation

Communication via the knx bus
Hide thumbs Also See for Synco 700 Series:
Table of Contents

Advertisement

Device identification
Device addressing
Notes
14/120
Building Technologies
HVAC Products
1.3.3

Device address

As described above, the network address consists of a combination of the area,
line and device address, for example 0.2.10, where 0 stands for the area, 2 for the
line and 10 for the device address.
0.2.150
Konnex TP1
0.2.1
The addressing of the devices must be planned at the design engineering stage.
Note the following points when assigning addresses:
• Each device address may be allocated only once within an area and a line.
Device addresses in the range 1 to 251 must be used for the maximum 64 bus
devices on a line (the same applies on a main line). Addresses 0, 150, 252, 254
and 255 are reserved for the following:
0
is used in each area or each line for the area or line coupler respectively.
150
is the factory-set device address for the OZW775 central communication unit
(device address 150 can be modified)
252
is used to connect the RMZ792 bus operator unit, i.e. the bus operator unit
uses this address if it is free, otherwise it starts at 252 and looks for the next
lower unused address.
254
is used to connect the ACS operator station (PC/Laptop with ACS7...
software) i.e. the OCI700.1 service tool uses this address if it is free,
otherwise it starts at 254 and looks for the next lower unused address.
255
is the factory-set device address of the Synco bus devices (see the notes
below).
The factory-set address 255 in the Synco bus devices prevents communication
problems in the commissioning phase. This is because devices with this address
do not send any data. However they can be controlled manually, and can receive
the new device address setting, for example.
The device addresses of the Synco 700 type RM... controllers can be set with the
RMZ790 and RMZ791 operator units (see section 4.2) or with the ACS7... software
(service tool OCI700.1, see section 5.2).
Remember not to use device addresses 150, 252 and 254 when addressing the
bus devices.
Basic documentation: Communication via the KNX bus
KNX (Konnex) and Synco
0.2.254
0.2.2
0.2.10
0.2.252
0.2.11
0.2.20
CE1P3127en
30.08.2007