Minor parameterization
Parameter numbers and
associated zones
Notes
Building Technologies
HVAC Products
7.3.2

RXB/RXL room controllers

• In ACS Service Applications > Parameter settings , open the menu tree of the
RXB/RXL room controller for which the zone address is to be set.
• Double-click the menu line "Communication" to open the operating page, and
select the zone for which the address is to be set. Double-click to open the
dialog box for entry of the address.
• Enter the zone address and click
7.3.3

Zone addressing with the QAX34.3 room unit

With the RXB/RXL room controllers, the zone addresses can also be set with the
QAX34.3 room unit (Minor parameterization, see section 5.6.1).
P008 Geographical zone (apartment)
P009 Geographical zone (room)
P010 Geographical zone (subzone)
P011 Time-switch zone (apartment)
P012 Time-switch zone (room)
P013 Time-switch zone (subzone)
P014 Heat distribution zone, air heater 1...31
P015 Refrig distrib. zone, cooling coil
P016 Heat distr zone heating surface.
P017 Refrig distr zone cooling surface 1...31
P018 Outside temperature zone
P023 Master/slave zone (group)
P023 Master/slave zone (room)
P024 Master/slave zone (subzone)
"P008" indicates that the "Geographical zone (apartment)" in the RXB/RXL room
controllers is parameter no. 008. For more information, refer to document
CM110385.
For the RM... controllers, the default value in the QAX34.3 room unit is "-1" rather
than "----". Both default values indicate that the zone is "out of service" and that no
process values are transmitted within the zone.
Basic documentation: Communication via the KNX bus
Communication via zone addresses
OK
to confirm the value entered.
1...126 -1 = Default value
0...63
1 = Default value
0...15
1 = Default value
1...126
1 = Default value
0...63
1 = Default value
0...15
1 = Default value
-1 = Default value
1...31
-1 = Default value
1...31
-1 = Default value
-1 = Default value
1...31
1 = Default value
1...126
1 = Default value
0...63
-1 = Default value
0...15
1 = Default value
75/120
CE1P3127en
30.08.2007