Siemens Synco 700 Series Basic Documentation page 57

Communication via the knx bus
Hide thumbs Also See for Synco 700 Series:
Table of Contents

Advertisement

Line couplers
Building Technologies
HVAC Products
The line address can only be set with ACS Service in programming mode.
1. Set the line coupler locally to programming mode. To do this, press the A5
"learning button". The red LED A4 lights up. (For a definition of "learning button
A4" and "LED A5" refer to the product and function description enclosed with
the Siemens couplers).
2. In ACS Service select Plant > Edit device list... to open the "Edit device list"
dialog box.
Programming mode...
3. Only the
4. Click
Programming mode...
line address in the range 1...15 (syntax A.L.0, from A.1.0 to A.15.0) and
click
Write
to confirm.
5. The new line address, 11, is adopted automatically by the line coupler when
the
Write
button is clicked.
6. Close the "Edit device list" dialog box with click on
Note:
• The red LED on the line coupler is extinguished once the line address has been
adopted.
• The line coupler automatically adopts the area address from the superordinate
area coupler. If there is no area coupler, the area address is set to 0 (zero).
• The Synco devices governed by the line coupler still have the "old" line address.
It is therefore essential to carry out the following steps 7, 8, 9.
Basic documentation: Communication via the KNX bus
Device addresses via ACS
button is available under "Address assignment".
. The "Address assignment" dialog box opens. Enter a
Close
button.
57/120
CE1P3127en
30.08.2007