Siemens Synco 700 Series Basic Documentation page 83

Communication via the knx bus
Hide thumbs Also See for Synco 700 Series:
Table of Contents

Advertisement

IP router as
area coupler
IP routers as couplers
between "worlds"
Building Technologies
HVAC Products
When the selected method of coupling is "IP router as area coupler", two or more
KNX areas are linked via an IP network. The IP routers are used to link main lines,
i.e. they must be addressed on the KNX side as area couplers.
1.0.0
Main line 1
Lc
Lc
1.1.0
1.2.0
N140/13
N140/13
KNX Area 1 (Main line 1) – IP network – KNX Area 2 (Main line 2)
IP routers are also used to link "worlds". This method of coupling is used to link two
or more KNX networks via an IP network
In this case, the IP routers connect the IP network to the KNX area line 0 of each of
the KNX networks concerned. The IP routers in all KNX networks must be set to
KNX address 0.0.0.
0.0.0
Area line 0
Lc
Lc
0.1.0
0.2.0
N140/13
N140/13
KNX Network 1 (Area line 0) – IP network – KNX Network 2 (Area line 0)
Basic documentation: Communication via the KNX bus
Large plants
IP network
IP Ac
N146
KNX
Lc
Lc
1.3.0
1.4.0
N140/13
N140/13
IP network
IP Ac
N146
KNX
Ac
1.0.0
N140/13
IP Ac
2.0.0
N146
Main line 2
Lc
2.1.0
2.2.0
N140/13
IP Ac
0.0.0
N146
Area line 0
Ac
1.0.0
2.0.0
N140/13
KNX
Lc
N140/13
KNX
Ac
N140/13
83/120
CE1P3127en
30.08.2007