PDU8000 Modular Precision PDC V2.0
User Manual
Specifies the upper alarm threshold in relative to the rated voltage. The value ranges from 105
to 125.
Specifies the duration for confirming an overvoltage alarm. The value ranges from 1 to 10.
Specifies the lower alarm threshold in relative to the rated voltage. The value ranges from 75
to 95.
Specifies the duration for confirming an undervoltage alarm. The value ranges from 1 to 10.
Specifies the overload alarm threshold in relative to the rated load. The value ranges from 100
to 120.
Specifies the duration for confirming an overload alarm. The value ranges from 1 to 10.
Specifies the overfrequency alarm threshold in relative to the rated frequency. The value
ranges from 1 to 10.
Specifies the duration for confirming an overfrequency alarm. The value ranges from 1 to 10.
Specifies the upper alarm threshold in relative to the rated current. The value ranges from 80
to 100.
Specifies the lower alarm threshold in relative to the rated current. The value ranges from 30
to 80.

7.4.3.6 Setting Wizard

On the Settings screen, tap Setting Wizard to access the screen.
Issue 03 (2018-01-25)
System overvoltage (%)
Overvoltage ack.time (s)
System undervoltage (%)
Undervoltage ack.time (s)
Overload (%)
Overload ack.time (s)
Overfrequency (Hz)
Overfrequency ack.time (s)
Upper load cur. thre. (%)
Lower Load cur. thre. (%)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
7 MDU Commissioning Guide
97