Huawei PDU8000 Series User Manual page 23

Modular precision pdc v2.0
Hide thumbs Also See for PDU8000 Series:
Table of Contents

Advertisement

PDU8000 Modular Precision PDC V2.0
User Manual
Item
Output circuit
breakers
Surge protection
Cabling
Environmental
friendliness
Overvoltage level
Operating
temperature
Relative humidity
Altitude
Table 3-3 Safety and EMC
Item
Safety
EMC
Issue 03 (2018-01-25)
Specifications
Single- or three-phase 16 A/20 A/32 A/40 A/63 A; maximum: 144
single-phase routes or 48 three-phase routes
Class C SPD in standard configuration
400 A/250 A/160 A input scenario: Cables can be routed in and
out from the top or bottom.
630 A input scenario: Cables can be routed in from the top and
out from the top or bottom.
RoHS, REACH
II
–5° C to +40° C
5%–95%, non-condensing
≤ 2000 m (If the altitude exceeds 2000 m, the device is derated
according to GB/T3859.2-93.)
Specifications
CCC, CE, TL
Conducted emission (CE)
Radiated emission (RE)
Voltage fluctuation and flicker
Harmonic current
Conducted susceptibility (CS)
Radiated susceptibility (RS)
Electrostatic discharge (ESD)
Electrical fast transient (EFT)
Surge
Voltage dip and short
interruption
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
N/A
EN55022 CLASS A
EN55022 CLASS A
EN61000-3-3
EN61000-3-11
EN61000-3-2
EN61000-3-12
IEC61000-4-6
IEC61000-4-3
IEC61000-4-2
IEC61000-4-4
IEC61000-4-5
IEC61000-4-11 2004
3 Overview
14

Advertisement

Table of Contents
loading

Table of Contents