Figure 5-39 Cutting holes in the rodent-proof meshes
Step 10 Reinstall the rodent-proof meshes.
Step 11 Reinstall the transparent covers of the input copper bar and N bar.
Step 12 Seal the gap between cables and the cabinet using flake sealing putty. (Remove the paper
protective film from the sealing putty and use the aluminum foil film together with the sealing
putty.)
Figure 5-40 Fill the holes with flake sealing putty
----End

5.4.4.2 Bottom Cable Routing

The following procedure applies to a single-input PDC.
Procedure
Step 1 Remove the rodent-proof meshes at the bottom and put them aside.