Alarm Reference - Huawei PDU8000 Series User Manual

Modular precision pdc v2.0
Hide thumbs Also See for PDU8000 Series:
Table of Contents

Advertisement

PDU8000 Modular Precision PDC V2.0
User Manual

8.2 Alarm Reference

Alarm
Name
Abnormal
board
comm.
Configuring
board ...
Failed to
configure
board
Board
quantity
inconsistenc
y
Abnormal
board power
supply
Main input
open phase
Main input
outage
Issue 03 (2018-01-25)
Alarm
Impact
Severity
The
Critical
communication
between the
MDU and
monitoring board
is interrupted.
Warning
The MDU is
configuring the
monitoring board.
Critical
Failed to
configure the
monitoring board.
The actual
Critical
number of
monitoring
boards is different
from the
configured
number.
The voltage of a
Major
power input to
the monitoring
board is less than
9.5 V.
Critical
A phase of the
input power has
no voltage or has
a voltage lower
than the threshold
(0–60 V).
Critical
The input power
has three open
phases.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
8 Maintenance Guide
Possible
Solutions
Cause
The
Check whether the
monitoring
CAN cable is in loose
board is
contact. If yes, connect
disconnected.
it securely.
The MDU is
N/A
configuring
the
monitoring
board.
The MDU
Use the latest upgrade
version does
package to activate the
not match the
board.
monitoring
board.
Monitoring
Check whether the
board
run indicator of the
fault.
monitoring board is
normal. If no,
The cable
replace the
has
monitoring board.
become
loose.
Check whether the
CAN cable is
securely connected.
Replace the
N/A
monitoring board.
The input
Check the input power.
power supply
is faulty.
The input
Check the input power.
power supply
is faulty.
120

Advertisement

Table of Contents
loading

Table of Contents