The user name is admin (preset password: 000001).
Figure 6-3 Setting Wizard
The figures are for reference only. The actual parameter values prevail.
Step 6 After the quick settings are complete, if the monitoring page displays alarms, clear the alarms.
For system security purposes, change the preset password upon first login.
Step 7 Turn on the input switches on the front panel of the PDC.
Step 8 Switch on the output circuit breakers except reserved circuit breakers in the PDC in sequence
to power on the corresponding devices and check whether the monitoring parameters on the
MDU screen are correct.
Step 9 (Optional) Power off the PDC.
1.
2.
3.
----End
Issue 03 (2018-01-25)
If this is the initial startup, set the language, time, date, network parameters, and system
parameters by using the Setting Wizard.
If this is not the initial startup and these parameters have been set before, the system uses
the existing settings by default.
Turn off the output switches in the PDC.
Turn off the input switches in the PDC.
Switch off the upstream power circuit breaker of the PDC.