Figure 5-40 Fill the holes with flake sealing putty
----End

5.4.4.2 Bottom Cable Routing

The following procedure applies to a single-input PDC.
Procedure
Step 1 Remove the transparent covers of the N bar and input copper bar, and put the
covers aside.
Figure 5-41 Removing the transparent covers of the N bar and input copper bar
Step 2 Connect the equipotential ground cables for the cabinet.