PDU8000 Modular Precision PDC V2.0
User Manual
Alarm
Name
Main input
underfrequ
ency
Main input
overload
Max. main
input cur.
exceed
Min. main
input cur.
exceed
Main input
surge
protection
abnormal
Main input
breaker off
Issue 04 (2021-04-13)
Alarm
Impact
Severity
Major
The input
frequency is 1.5
Hz lower than
the configured
frequency. The
frequency
setting range is
50–60 Hz.
Critical
A phase input
current of a
route exceeds 1
time of the
rated current
(multiple: 1–
1.2;
confirmation
time: 1–10s).
Warning
A phase input
current of a
route exceeds
0.8 time of the
rated current
(multiple: 0.8–
1).
Warning
A phase input
current of a
route is lower
than 0.6 time
of the rated
current
(multiple: 0.6–
0.8).
Major
Any dry contact
on the SPD
connecting to
the mains input
is disconnected.
Warning
A mains switch
has changed
from ON to
OFF.
Copyright © Huawei Technologies Co., Ltd.
8 Maintenance Guide
Possible
Solutions
Cause
The input
Check the input
power
power.
supply is
faulty.
The system
Check all output
is
load power.
overloaded.
The system
Check all output
is
load power.
overloaded.
N/A
N/A
The SPD
Switch on the SPD
circuit
circuit breaker, or
breaker is
replace the SPD
switched
module.
off, or an
SPD module
is damaged.
N/A
N/A