8.1 Routine Maintenance
Routine maintenance is performed on a regular basis when the equipment is
running properly to find out and eliminate defects or potential risks in a timely
manner.
Table 8-1 Routine maintenance for the PDC
Maintenance
Item
Three phase
power
indicators
Surge
protection
module
Issue 04 (2021-04-13)
8
Mai
Operation
nten
Guide
ance
Inter
val
Mon
Check the
thly
luminance of
the indicators.
Mon
Check the
thly
status of the
surge
protection
module
indicator and
circuit
breaker.
Copyright © Huawei Technologies Co., Ltd.
Maintenance Guide
Expected
Exception Handling
Result
The three
Replace the indicator that
phase
generates no or dim light.
power
indicators
are steady
on.
● The
● If the indicator of an
surge
SPD module is red,
protecti
replace the SPD
on
module.
module
● If the circuit breaker is
indicator
switched off, switch it
is green.
on.
● The
circuit
breaker
is
switched
on.
8 Maintenance Guide