Siemens SITOP UPS1600 Manual page 131

Hide thumbs Also See for SITOP UPS1600:
Table of Contents

Advertisement

Data
Calculated battery 3 capacity
[0.1 Ah]
Calculated battery 4 capacity
[0.1 Ah]
Calculated battery 5 capacity
[0.1 Ah]
Calculated battery 6 capacity
[0.1 Ah]
Input voltage [0.01 V]
Input current [5 mA]
Output voltage [0.01 V]
Load current [5 mA]
Measured charge current [1 mA]
Battery voltage [0.01 V]
Output current [5 mA]
Charge voltage [0.01 V]
Fill byte(s)
Valid configuration
Number of batteries
Fill byte(s)
Battery 1 change recommended
Battery 2 change recommended
Battery 3 change recommended
Battery 4 change recommended
Battery 5 change recommended
Battery 6 change recommended
Battery 1 Connection Fault
Battery 2 Connection Fault
Battery 3 Connection Fault
Battery 4 Connection Fault
Battery 5 Connection Fault
Battery 6 Connection Fault
Battery 1 temperature [1 °C]
Battery 2 temperature [1 °C]
SITOP UPS1600 / UPS1100
Manual, 04.2016, A5E37775406-6-76
Description
Battery 3: Calculated battery capacity.
Battery 4: Calculated battery capacity.
Battery 5: Calculated battery capacity.
Battery 6: Calculated battery capacity.
Input voltage: Measured rms value of the supply voltage at the
input of the SITOP UPS1600.
Current measured at the input of the SITOP UPS1600.
Voltage measured at the output of the SITOP UPS1600.
Load current measured at the output of the SITOP UPS1600.
Measured battery charge current of the SITOP UPS1600.
Measured battery voltage of the connected battery modules.
Load current measured at the output of the SITOP UPS1600.
Voltage used to charge the batteries during the constant charging
process.
-
Valid configuration: Indicates whether the software parameters or
the parameters at the rotary switches are used. The corresponding
setting should be made at the rotary switch for the buffer thresh-
old.
Number of connected battery modules. Here, only the
SITOP UPS1100 battery modules (coded batteries) are counted.
-
Battery 1: Battery replacement recommended: The battery capaci-
ty is not sufficient for the defined buffer time.
Battery 2: Battery replacement recommended: The battery capaci-
ty is not sufficient for the defined buffer time.
Battery 3: Battery replacement recommended: The battery capaci-
ty is not sufficient for the defined buffer time.
Battery 4: Battery replacement recommended: The battery capaci-
ty is not sufficient for the defined buffer time.
Battery 5: Battery replacement recommended: The battery capaci-
ty is not sufficient for the defined buffer time.
Battery 6: Battery replacement recommended: The battery capaci-
ty is not sufficient for the defined buffer time.
Battery1: Connection fault
Battery2: Connection fault
Battery3: Connection fault
Battery4: Connection fault
Battery5: Connection fault
Battery6: Connection fault
Battery 1: Battery temperature
Battery 2: Battery temperature
Engineering and remote access
3.7 Cyclic and acyclic data
Data type
Unsigned16
Unsigned16
Unsigned16
Unsigned16
Unsigned16
Unsigned16
Unsigned16
Unsigned16
Unsigned16
Unsigned16
Unsigned16
Unsigned16
3 x Unsigned8
Unsigned8
Unsigned8
7 x Unsigned8
Unsigned8
Unsigned8
Unsigned8
Unsigned8
Unsigned8
Unsigned8
Unsigned8
Unsigned8
Unsigned8
Unsigned8
Unsigned8
Unsigned8
Integer8
Integer8
131