Environmental conditions
Table 10- 1
UPS1600
Ambient temperature
Transport and storage
temperature
Humidity class
Degree of pollution
Mechanical
stress in operation
Damaging gases
Air pressure
SITOP UPS1600 / UPS1100
Manual, 04.2016, A5E37775406-6-76
6EP4134-3AB00- ... (10 A)
-25 ... 70 °C for natural convec-
tion (self convection)
Tested according to:
EN 60068-2-1 cold
•
EN 60068-2-2 dry heat
•
EN 60068-2-78 humid heat, constant
•
EN 60068-2-14 temperature change
•
Remark: The service life of the UPS1100 battery modules (decrease to 50% of the original capac-
ity) depends on the battery temperature, at approximately 20° C: 4 years, 30 °C: 2 years, 40 °C: 1
year
-40 ... 85 °C
Tests (packed for shipping) according to:
EN 60068-2-1 cold
•
EN 60068-2-2 dry heat
•
EN 60068-2-30 humid heat, cyclic
•
Climatic class 3K3 according to EN 60721, 5 - 95 % no condensation
2
Tested according to:
EN 60068-2-6 Vibration, test Fc:
•
3.5 mm deflection in the range 5 – 9 Hz
1 g acceleration in the range 9 – 150 Hz
EN 60068-2-27 shock, test Ea:
•
acceleration 150 m/s
2
Tested according to:
EN 60068-2-42 sulfur dioxide
•
EN 60068-2-43 hydrogen sulfide
•
Operation:
1080 - 795 hPa (-1000 - 2000 m)
•
For operation at altitudes of 2000 m up to 6000 m above sea level:
•
output must be derated by -7.5% / 1000 m or
the ambient temperature must be reduced by 5 K / 1000 m
see Image 6-5 Altitude derating (Page 148)
Storage:
1080 - 660 hPa (-1000 - 3500 m)
•
6EP4136-3AB00- ... (20 A)
-25 ... 60 °C for natural convec-
tion (self convection)
15 A (derating) at 60° ... 70° C
, test duration 11 ms
10
6EP4137-3AB00- ... (40 A)
-25 ... 60 °C for natural convec-
tion (self convection)
30 A (derating) at 60° ... 70° C
169