SITOP UPS1600 / UPS1100
Manual, 04.2016, A5E37775406-6-76
Alarm Text
F
Wrong battery polarity
MD
Reserve
MR
Insufficient charge level
MR
Deep discharge battery
D
Battery defective (battery
index: x)
D
Battery deep discharged,
charging not possible (bat-
tery index: {1:d}).
MD
Battery temperature high
(battery index: {1:d}).
MD
Battery temperature low
(battery index: {1:d}).
D
Communication error to
battery (battery index: {1:d}).
D
Wrong battery configuration
(battery index: x).
MD
Battery parameters corrupt
(battery index: {1:d}).
D
Fuse is defective (battery
index: x).
Help Text
Wrong battery polarity - check battery connections.
Battery charge level presently too low to reach the
set buffer capacity.
Battery is deep discharged - no buffering possible.
Battery defective - check the fuse and the battery
voltages.
Battery is deep discharged - replace battery.
Battery temperature too high - battery life will be
shortened.
Battery temperature too low - reduced output cur-
rent
Communication with formerly known battery is no
longer possible - check communication.
Different battery types connected. Only batteries of
the same type can be operated together.
Battery defective - replace battery.
Fuse is defective.
Troubleshooting