Siemens SITOP UPS1600 Manual page 98

Hide thumbs Also See for SITOP UPS1600:
Table of Contents

Advertisement

Engineering and remote access
3.5 SITOP UPS Manager
Configuring the local computer as master PC
1. Select "General settings > Device configuration".
2. Activate the "Ethernet" checkbox and the "Master-PC" checkbox.
3. If you are prompted as to whether you want to restart the SITOP UPS Manager, confirm
this with "Yes".
The SITOP UPS Manager is restarted.
4. Select "Hardware configuration > Ethernet configuration".
5. Enter the IP address of the master PC in the field "IP address of the master PC". A
selection box is displayed next to field "IP address of the master PC", which lists all of the
available IP addresses of the client (PC/PG). Selecting an IP address automatically
inserts this address in field "IP address of the master PC".
Note
Also at the local computer, the IP address of the master PC must be specified in the
SITOP UPS Manager if a master-slave configuration is to be used.
6. Enter the IP address of the SITOP UPS1600 in the "IP address of the DC-UPS" field.
7. If you are prompted as to whether you want to restart the SITOP UPS Manager, confirm
this with "Yes".
The SITOP UPS Manager is restarted.
The connection lamps light up green, the connection as master PC to the SITOP UPS1600
is established, if the (local) PC is connected as master PC to the SITOP UPS1600.
Configuring the client as slave PC
1. Select "General settings > Device configuration".
2. Activate the "Ethernet" checkbox and the "Slave PC" checkbox.
3. If you are prompted as to whether you want to restart the SITOP UPS Manager, confirm
this with "Yes".
The SITOP UPS Manager is restarted.
4. Select "Hardware configuration > Ethernet configuration".
5. Enter the IP address of the master PC in the field "IP address of the master PC".
6. If you are prompted as to whether you want to restart the SITOP UPS Manager, confirm
this with "Yes".
The SITOP UPS Manager is restarted.
The connection lamps light up green, the connection as slave PC to the master PC is
established, if the (local) PC is connected as master PC to the SITOP UPS1600.
98
SITOP UPS1600 / UPS1100
Manual, 04.2016, A5E37775406-6-76